FeaturesTime delay adjustments - 5 to 30 min at minimum, 3 minimum if no activity after 30 s at walk through mode, 5 s for 10 min with dip switch setting at test modeMinimum to maximum sensitivity adjustment0 to 1000 VA tungsten, ballast, E-ballast, LED driver, 1/4 hp motor load requirement for each relay at 120 VAC, 0 to 1800 VA ballast, E-ballast, LED, load requirement for each relay at 277 VACPulse count processing eliminates false OFF without reducing sensitivityDetection signature analysis eliminates false triggers and provides immunity to RFI and EMIZero crossing circuitry reduces stress on the relay and results in increased sensor lifeTime delay adjustment from 30 s up to 30 minAdjustable unit sensitivity from 20% to 100%Light level sensor holds lights off when ambient lighting is above the preset levelCustom 2-tier fresnel lens enhances detection at the desktop levelSensor coverage tested to NEMA guide publication WD 7-2000Patented voltage drop protectionFor safety, there is no leakage to load in the OFF mode and sensor is safety groundedLED indicates occupancy detectionCompatible with decorator wallplatesTungsten ballast E-ballast load typeTurns lighting on and off based on occupancy and ambient light levelIt replaces existing wall switches and fits behind a standard decorator wallplate